Electronic – How to find the exact number of turns for a power transformer

powertransformer

The input and output voltages of a power transformer allow us to derive the ratio of turns on the primary and secondary coils.

My question is how to find the exact number of turns of primary and secondary coils if input and output voltages and power in KVA are given?

For example a transformer with the characteristics Vp=11kV, Vs=400V and power=100KVA. Can we calculate the number of turns from this?

Best Answer

I'm going to take a stab at this and maybe if I'm wrong about the material specifications of silicon steel laminates someone can point this out. There is almost enough information in the question to figure this out, given that you have to make some estimations about the size of the transformer....

I'd start from basics, B = \$\mu H\$ and, recognizing that the peak flux density of silicon steel\$^1\$ should be limited to about 2 teslas, H can be calculated from an estimation of the magnetizing current likely for a 100 kVA single phase power transformer.

Vp=11kV, Vs=400V and power=100KVA

Primary current will be about 10 A for full load (from above statement by OP) and, magnetization current will be about 5% of this (say) 0.5 A. Peak Mag Current will be 0.71 A. Noted. Also, using the classic B-H formula: -

B = \$4\pi\times 10^{-7}\times 40,000\times H\$ or

H = \$\dfrac{B}{4\pi\times 10^{-7}\times 40,000}\$ and for B = 2 teslas, H = 39.8 ampere-turns per metre.

What are ampere turns per metre - "amps" everyone knows, "turns" everyone knows and the "per metre" refers to the mean magnetic length of the core. For a toroid it is the average diameter of the ring multiplied by \$\pi\$. For a power transformer this might easily be 3 metres (a stab in the dark really because the kVA are out of my league!!)

So we have H = about 40 A.t/m and we know the amps (peak) at about 0.7 and I'm guessing the length is 3m. This means the number of turns is going to be: -

\$\dfrac{40\times 3}{0.7}\$ = 171 turns - can a sanity check be done on this I'm thinking?

I could estimate the cross section of the transformer core at 0.1m\$^2\$. Then I could calculate reluctance of the core based on this formula: -

Reluctance = \$\dfrac{effective\space length}{permeability\cdot effective\space area}\$. Plugging in real numbers we get: -

\$\dfrac{3m}{4\pi\times 10^{-7}\times 40,000\times 0.1m^2}\$ = 596.8

Knowing reluctance and turns I can calculate inductance: -

Inductance = turns-squared / reluctance = 171\$^2\$/597 = 49 henries.

Then I could estimate the reactance assuming 50 Hz and get 15.4kohms

Then I could calculate the magnetization current based on 11kV = \$\dfrac{11,000}{15,400}\$ = 0.71 amps.

This isn't far off from where I started when I assumed 0.5 A magnetization current so I guess the primary turns will be around about 171 turns and if the secondary voltage is 400 V then the secondary turns are about 6.218, so if I assume there are 7 secondary turns, the number of primary turns will be about 193.

I have no idea how far off this will be so don't go winding this at home and throwing a couple of wires over the nearest 11kV supply feed!


\$^1\$ Silicon steel is the likely candidate for the core of a big power transformer and this material has a relative permeability, \$\mu_R\$ of 40,000. See table halfway down this page. I'm no expert on power transformers so don't shoot me if it's wrong!!

EDIT - contrary to the site that states rel permeability is 40,000, wiki states \$\mu_R\$ for "electrical steel" is more like 4,000. This would make H, magnetic field strength calculated above more like 398 A.t/m. This would make the number of turns for the primary more like 1700. Anyone any idea what \$\mu_R\$ is going to be?