Electronic – Solenoid stays on when output turned off

outputplcsolenoidsolid-state-relay

I have a power supply with 12V running into a the common on my PLC. Output 0 on the PLC is wired into a solenoid. The negative on the solenoid runs into the ground on the power supply completing the circuit.

When I power up the PLC and the the external power supply all outputs on the PLC are off and the solenoid is off. When I activate Output 0, my solenoid clicks on as expected. However, when I turn Output 0 back off, the solenoid stays on. The solenoid only turns off if I physically remove the ground wire.

edit:

The diagram below gives some insight. Power supply wired to Pin 17. Output 0 (pin 10) wired to solenoid. Solenoid is wired back to ground on the power supply.

If I give the command to turn output 0 on, the solenoid comes on. If I give the command to turn output 0 off, the solenoid stays on.

enter image description here

Link to my cheapo solenoid. http://www.amazon.com/gp/product/B008IG7SWQ/ref=oh_details_o04_s00_i01?ie=UTF8&psc=1

Best Answer

A common problem. Its all to do with the coil on the device, I have had the same issue with energising contactors before.

Try instead to used the PLC output to energise a small relay and switch the solenoid via a relay contact. That should solve your problem.