Electronic – What kind of protection do these Ethernet “surge protection” diodes provide

differentialdiodesethernetprotectionsurge-protection

I was considering a network run outside of my home, and purchased a super-cheap "Ethernet Lightning Protector" because there was little to lose, and I wanted to understand its workings.

Ethernet surge protector

Below you can see the insides after I'd opened it:

Protection didoes

Bottom of PCB

The first thing I noticed was the superb manufacturing quality (ahem). As for the design, it appears to be just clamping diodes.

I was expecting TVS's, or perhaps varistors, but I want to say they're Zeners because of the typical clear-red appearance, but I wasn't sure if there were other diodes/components of that look. They have no markings on them other than the single red band in the middle.

Q1: Anyone care to say if these are for sure Zeners?

Q2: As for protection, what would this actually provide? ESD protection? Could this really be considered lightning protection?

Also I'm wondering how these diodes would help. I know Ethernet uses a differential signal… The diodes appear to have their anodes at the "shielding" of the jacks.

Q3: So this literally wouldn't do anything without shielded cable (STP)?

That being said, I've little experience with Ethernet hardware design.

Q4: It seems that "all" or most Ethernet devices use transformers, so can it be said that there is some protection already inherent?

Best Answer

If the PCB itself can be trusted, they are diodes. They also look like diodes.

Wired as they are, they will short any data line to any other if the potential between them reaches twice the breakdown of the diode - the way they are wired, they are effectively in series.

If the cables are grounded, then the diodes will short the over voltage to ground through the shield.

It will probably do something. Whether it is enough is hard to say.

If you really want protection, use something that you have to connect to an earth ground. That will dump over voltage to ground rather than through the ground wire on your equipment.