Removing neon transformer center tap

dischargegroundhigh voltagephysicstransformer

I have recently acquired an old neon transformer (rated 12kV) for conducting some low temperature plasma experiments. It is the mid-point grounded style with a center tap on the secondary coil. I had overlooked these details and I really need to have a single lead at full potential, so I'd like to remove the center tap ground and ground one side of the secondary. I'm under the impression that this will allow the opposite lead to supply a full 12 kV potential (open circuit, that is).

Will removing the center tap and grounding one end pose any threat to the transformer (such as arcing through the potting material) and how should I ground the opposite end/is it necessary to install a separate ground rod or can I use mains?

PS the NST (neon sign transformer) is an Allanson 12kV 30mA (no-GFI)

Thanks in advance,
Mitchell

Best Answer

Removing the center tap, even if it was something you could just do, would be a very bad idea. The beauty of having a center-tapped transformer is that each side of the tap only has to be rated for half the total voltage, whereas if you have the full voltage on one end you risk destroying the insulation, and thus the transformer.

Your best bet would probably be to find another transformer, one that is end-point grounded. Whether it be a neon transformer, an oil burner ignition coil, or (NOT RECOMMENDED), a microwave oven transformer, getting a transformer that is designed to have the full potential on one lead would be ideal.

So my recommendation would be to not remove the center tap, as it could cause all sorts of problems, even ones that you would never expect.