Electrical – Reason for High voltage difference between Ground and neutral wire in 3 phase system

acpowerpower-engineering

I have following reading of voltages:

  1. RY 397V

  2. RB 398V

  3. YB 393V

  4. RN 231V

  5. YN 227V

  6. BN 228V

  7. RG 386V *

  8. YG 385V *

  9. BG 10V *

  10. NG 216V *

If you clearly observe data above phase-to-phase voltages are good and phase-to-neutral voltages are also good, but when I measure phase voltages with respect to ground unusual value is observed which should be actually somewhat equal to phase-to-neutral voltage. Also the neutral-to-ground voltage is too high, but should be minimum. Now the problem is it is not affecting the normal electrical equipment, but highly sensitive equipment like UPS doesn't take it as a healthy voltage. So what might be the cause behind it?

Best Answer

schematic

simulate this circuit – Schematic created using CircuitLab

Figure 1. The likely cause of the low voltage reason on the blue phase.

It sounds as though your supply is from a star (European term) or wye (American term) connected transformer. Normally the star point, marked 'N' for neutral, is connected to earth to "neutralise" it.

In your case it seems as though either

  • the blue phase has been earthed for some reason or
  • that the transformer secondary star / wye point was not grounded but has now developed an earth fault on one phase.

The second arrangement can be used in the right circumstances to give single-fault tolerance of a ground fault. The circuit will continue to operate (as you have noticed) until a second ground fault occurs. When this is done it would be normal to add ground fault detection to warn of the event. Three bulbs in place of the voltmeters would suffice: when a ground fault occurs that lamp would go out.

The problem with this arrangement is that devices rated for 230 V to ground now have 400 V to ground. This may stress the insulation, causing early failure, and also provides a higher shock hazard to maintenance personnel.

schematic

simulate this circuit

Figure 2. Earthing of star / wye point on transformer. This is standard European practice.

I'd recommend understanding the design intent, examining the system and repair, if required.