Electrical – Use ACS712 current sensor in two-phase electrical system

accurrent measurement

I'm thinking about using the Allegro ACS712 current sensor for measuring house equipment current consumption (for example TV). The issue I'm facing is that my house energy supply is built around two 110VAC phases. My equipment works with 220VAC but not in Live-Neutral configuration, but in Main1-Main2 configuration.

Having the two connections "active" confuse me a bit… I don't know how to proceed. Should I use two sensors, one for each main? Should I measure only one cable? Will the equipment current flow from only one main or from both of them?

Any guide will be appreciated.

Thanks a lot!

EDIT:

This image represents what I want to do:

Block diagram for mains power current measurements using ACS712

Also, the values you see stated were measured by my multimeter. Maybe this helps to sum up what I was trying to say and reduce confusion.

Best Answer

It sounds like you have a standard North American "Split Phase" electrical supply as supplied to most residential homes. As you mention: you have two "Line" connections plus a Neutral.

Most of your loads are 120 Vac and come from one of the Line conductors to Neutral. The remaining loads are 240 Vac and come from both of the Line conductors.

What you need to measure depends on what you are trying to measure. There are a couple of possibilities: you are trying to measure the current consumption of the entire household OR you want to measure the current consumed by only a single load.

If you are trying to measure the current consumed by the entire household, you have to measure the input current on BOTH of the Line conductors. This is because most loads return to Neutral but the remaining loads return to the other Line conductor.

If you are trying to measure the current consumed by a single device, you need to have current sensors on the total number of active power conductors (Line & Neutral) minus one.

In other words, if your load is strictly 240 Vac with NO Neutral connection, you need only ONE current sensor. OR: if your load is strictly 120 Vac with no connection to the other Line conductor, you also need only ONE current sensor.

However, if your load is something like an electric clothes dryer or electric range, you need TWO current sensors. That is because part of the load is between the two Line conductors, the remaining load is between either of the two Line conductors and Neutral.

[Edit]

Based on your revised question, I would say that you need only ONE current sensor. It doesn't matter which Line conductor the sensor is connected in series with.