From this article: Power Tips: Power converter topology… they say that:
Moreover, buck-converter duty cycles become extremely small in
high-voltage AC/DC conversion. For a 440VAC to 15VDC conversion, the
duty cycle could be smaller than 2% in a DCM buck converter. When
operating the converter at a high switching frequency, it is possible
to hit the controller minimum on-time limitation; for example, the
UCC28911 requires a 420nS minimum on time. In other words, if you use
the UCC28911 in a 440VAC to 15VDC conversion as a buck-converter
controller, the converter must operate at a switching frequency lower
than 45kHz.
What I understand is this. Let's say the duty cycle is 2%. If the switching frequency is 60 kHz, then the minimum time would be 0.02*(1/60k) = 333 ns. And the UCC28911 wouldn't start because their minimum time is 420 ns according to the datasheet. Then the article says that the converter must operate at a switching frequency lower than 45kHz. However, the datasheet says the minimum switching frequency is 420 Hz. Would the controller adjust the frequency itself if this situation with the minimum time happen?
Best Answer
As per the datasheet:
https://www.ti.com/lit/ds/symlink/ucc28911.pdf?ts=1591886894954&ref_url=https%253A%252F%252Fwww.ti.com%252Fproduct%252FUCC28911
as long as the loading isn't too light and the voltage conversion range is too large that the lower frequency limit is hit, the controller shall regulate the switching frequency according to the operating case e