Electronic – Do circuit breakers trip on Apparent or True Power

apparent-powercircuit breakerreal-power

The thermal and magnetic protection for AC circuit breakers take into account both the timing and the magnitude of the AC current passing through.

Does a standard circuit breaker trip on the current related to the Apparent (kVA) Power, or the current related to the True (kW) Power?

I would understand they act on the current related to the True Power (kW), and the amount of Reactive Power (kVAr) should in some way (?) affect the tripping curve (such as the B, C or D in the miniature circuit breakers) or is there no effect and just the current related to the Apparent Power is which is effectively sensed by the internal coil?

Edit 1:

So Far:

  • The Circuit Breaker should act on RMS Current \$I_{RMS}\$, which is the current acting on the Thermal (Power Dissipation Time Average, over a Bimetalic element) and Magnetic (Magnetic Flow Time Average, magnetizing a ferromagnetic element) actions in a Circuit Breaker (at least, those depicted, whose operation is based on these actions).
  • The Power Factor of the load have no impact on the tripping action, hence the RMS Current, as in the Apparent Power (kVA), is the key factor, regardless the load is Resistive (kW) or Capacitive|Inductive (kVAr).

Edit 2:

Some confusions I have read in answers and comments.

  • Note that a trip in a CB do not imply a fault. They are absolutely different concepts. A trip can be caused by an steadily increase of the load connected to the CB, without involving any electrical fault at all. (The operation is affected and that would constitute a fault, but a design, operational, or management fault, not strictly an electrical one, at least compared with classical faults, discussion which escapes the scope of this question…).
  • A trip, hence, do not imply a drop in the supply voltage. That is a mistake, from the above confusion. We straightforwardly can think on counterexamples of this (which one?).
  • Apparent Power, Reactive Power, True Power, Impedance are definitions, and the question uses them. At the very end, Breakers and Distribution Panels are used to control Power.

enter image description here

enter image description here

Best Answer

Thermal and magnetic circuit breakers trip on current, not power.

They know nothing about the voltage in the circuit until the contacts open and start to arc.


enter image description here

Figure 1. A single-phase circuit breaker. Image source Electrical Engineering Portal.

Note that in the single-phase circuit breaker there are only two terminals. When the circuit breaker is closed the voltage difference between the two cable terminals will be very small due to the very low contact resistance. As a result, the circuit-breaker is unaware of the voltage or power being drawn through it.

The three-phase breaker is usually three individual breakers with a mechanical link between them so that they all switch off if there is an over-current on one phase. Usually there will be no cross connection between the phases which would be required if voltage (or power) measurement was being done.


From the OP's self-answer below:

... so, a Circuit Breaker is actually tripping to the current related to the Total Power (kVA).

No, you are assuming that the voltage is constant during the fault. In general the voltage will drop / droop during a fault and that means that it could trip on a wide range of kVA. The circuit breaker trips on current only. You can, if it's useful, calculate the maximum kVA that the breaker can handle at nominal line voltage but that's not what you are asserting.