Grid tied inverter voltage is slightly higher than that of grid but once the tie is closed voltage will be equal then how the current will be injected from the inverter
Electronic – Grid tied inverter
inverter
Related Solutions
Electrons are fungible — you can't tell the difference between one electron and another. Therefore, no actual switching is required — your power meter simply measures the net power consumption of your house, which is the difference between what your loads require and what the solar array is providing.
In some jurisdictions, if that net value becomes negative — in other words, you're generating more power than you need — the meter does measure the power that you're feeding into the grid separately, because the rate at which you sell power to the grid is not the same rate at which you purchase it.
(1) The inverter output will be exactly the line voltage, having raised the (local) line voltage according to the source impedance of the supply line and the current developed As the inverter is connected to the line, its output is the (locally measured) line voltage by definition. The "meter spins backwards" when generation exceeds use, because it senses the current direction. Often there would be separate meters for consumption and generation.
simulate this circuit – Schematic created using CircuitLab
This is a residential distribution network, your house is No.2, the third from the pole transformer and the only one with solar power. Currently it's in shadow, so the line voltage reduces slightly further from the pole, and the last house (No.3) sees 109V.
When the sun comes out, the line voltage at the pole remains 115V, but your local line voltage also becomes 115V.
No. 1 is now fed from both sides and it's line will rise from 113V to 114V, and No.3 is still 2V below your line voltage, now seeing 113V.
Weather Line No.1 No.2 No.3
Cloudy 115V 113V 111V 109V
Sunny 115V 114V 115V 113V
(2) Where are you and what connection regime are you in? If you're in the UK and conforming to the G83/2 standard for a single phase residential connection, the answer is up to 16A. (Higher output is allowed on a separate standard, G59/2 for 3 phase connections). Any excess power is simply not drawn from the panel (assuming this is a grid tie system with no local storage)
None of this applies outside the UK.
(3) Pretty much nothing visible, maybe a very slightly higher voltage and marginally cleaner waveshape (assuming your inverter is legal and conforms to the applicable standards, including harmonic distortion.
The G83/2 specification illustrates the requirements for protection against overvoltage, out of tolerance frequency and waveform shape - and the all-important consideration of disconnecting immediately if the grid fails, to prevent electrocuting the engineers trying to repair it!
Here's an article on the rules in California to get you started on the US standards - which may well vary from State to State.
Grid regulation is a topic in itself - it isn't automatic, someone monitors it and adds or removes generation capacity to keep its parameters (voltage and frequency) within limits.
One characteristic of traditional (spinning metal) generators is that as you load them, they slow down a little, which reduces their output voltage and their contribution to the grid - transferring their load to others, which slow down in turn - arriving at a concensus on the actual mains frequency. You can watch this process in the UK in real time here. At the moment, it's reading 50.007Hz, so there's no need for additional capacity, but if it falls to 49.9Hz, phone calls will be made and some other power source will be turned on...
The importance of this for grid tie inverters is the way they can affect demand and power flows in the short term in unpredictable ways, taht the grid isn't currently designed for.
Related Topic
- Electronic – get high DC current in grid tied inverter output
- Electrical – How is the amount of outgoing power controlled in a grid tie inverter
- Electrical – Connecting a 48 V battery to a grid tie inverter
- Electronic – Can a double conversion UPS energize grid-tied micro inverter solar array during power outage
Best Answer
The inverter voltage has to be slightly higher than that of the grid to make the current flow to the grid.
It's like water flowing between two tanks. If both tanks are at the same level there is no flow. You need a difference in heights to make the water flow. You need a difference in voltage to make current flow.