Electronic – how does this occupancy-sensor switch not need neutral

electricity

Note, I don't think this belongs in DIY; it's a bit more complicated than that.

I bought a Lutron Maestro occupancy sensor switch, and was perplexed to learn that it doesn't need a neutral in the switch box (they brag about this as a feature, and the instructions don't mention it).

http://pdf.lowes.com/installationguides/027557983136_install.pdf

Note that in addition to the line and load (black) wires, the switch has both a bare wire and a green wire (drawing on top of 2nd page). I'm thinking maybe the bare wire (which is connected to the yoke) is the "real" ground and the green one carries the return current from the sensor and logic circuitry. But the instructions say to tie both to the switch box's ground

This seems most odd to me. I thought the whole point of NEC rule 404.2C, which requires a neutral in every switch box (with a few exceptions), is that when "smart" devices such as this are installed, that no currents are introduced into the grounding system.

I wonder what's going on. Is it:

  1. Does the switch somehow not return any current to ground ? I'm not sure this is possible, unless there's some sort of charge pump or something working off the hot wire(s).

  2. Does the switch's logic sensor and logic circuitry use so little current that it is deemed (by UL and/or NEC) acceptable for those currents to flow through the EGC ? I did not know there was a threshold.

  3. This is only meant for retrofits into older construction not compliant with 404.2(C) ? Would this even be legal ? And if so, why don't the instructions say to tie one of the wires (presumably the green one) to a neutral if it is present ?

Best Answer

There is more than one way to skin this cat

Manufacturers over the years have employed several solutions to the problem of how to power switch "smarts" (in occupancy sensors and the like) without using the neutral wire (as the mandate for having the neutral at the switch location first appeared in the 2011 NEC, and installations prior to it often omitted it in order to reduce cost and conserve truck-space, aka the electrician's version of BoM space, when switch loops were used):

  • Some devices (like the ones in the OP's post) use the equipment ground as a return path. This means they require a grounding conductor in the box in order to install successfully, and are largely limited to retrofit applications in homes and other small buildings to avoid excessive current on grounding conductors. (It also means that you shouldn't put one downstream of a GFCI to minimize the risk of nuisance tripping.)

  • Other devices "trickle" their operating power through the load, relying on circuitry inside to make sure that current flow through the load is not excessive and to maintain a powered state whether the internal switching elements are on or off. This means that they require a minimum load to guarantee functionality and often cause sensitive loads like LED lights to light dimly if such a minimum load (such as an incandescent bulb, or a dedicated return capacitor such as a Lutron LUT-MLC) is not present. However, they can be used in older installations where ground wires are not present.

  • Last but not least, there are a few wallbox devices that rely on a long-life primary battery (such as a CR123) for power. (Some of Intermatic's timers do this, most notably, and so do some wall-mounted fan remotes.) This, of course, means you have the downside of having to change a battery every few years in a device that you normally wouldn't expect to have a battery to change.

There is one more point to discuss with the Lutron Maestro occupancy sensor the OP asked about, and that is the distinction between the green and bare wires. Many devices that use the grounding conductor for return have a single connection to the grounding system, shared between the yoke ground connection and the return path from the internal circuits. However, the Lutron devices separate these, with the bare wire connected to the yoke and the green wire connected to the internal circuits. This allows them to be converted to neutral-based operation simply by slipping a sleeve of white spaghetti tubing over the green wire and nutting it in with the neutrals instead of the grounds (some higher-end Lutron Maestro devices already come with the tubing piece and instructions for its use, even).

Related Topic