On the 3 phase system, it is possible to supply a 380V load using 2 phases, say L1 and L2.
I understand that the phases alternate and that one phase acts as a return path for another, but this doesn't seem to always be true when looking at the graph.
Lets say I supply a 380V coil with only the Red and Purple phases, at time 0.1 both will be in the positive half. Now, does this mean that there wont be a return path at time 0.1? What will actually happen to the load at the instant where both phases are either in the positive half or negative half?
Best Answer
Figure 1. Voltage on red phase relative to purple phase. The lower set of arrows shows the resultant 'waveform' samples referenced to a straight X-axis.
Have a closer look. The red and purple cross at 1/12 (not 1/10) which is 30° into the purple cycle.
All that matters is where they are relative to each other.
Note also that the phase to phase voltage is 30° ahead of the red phase.
simulate this circuit – Schematic created using CircuitLab
Figure 2. The red-purple phasor (green) is 30° ahead of the red phasor.