we both agreed on the value of series impedance which is (12.82[82] ) however what i think he did wrong is the value of secondary reflected on primary
since it is Y-delta
7967/480 = root(3) a hence a will be 9.6
so the vs* = 480 * 9.6
=4608
Is(phase) will be (200k/(3(480)) = 80,16[-25.84]
NOW vp(phase) = vs* + (Is/a) * Z(eq)
4608+107[56.16]
=4668[1.1]
so vp(line)=root 3 v(phase)
8086[1.1]
Vr in my calculation (4668-4608)/4608 = 1.3 %
Is my answer correct and the solution did a mistake if so ok but if not what did I miss in my calculation?
hope that you help me with this ! :/
Best Answer
Take a look at the first sentence of the question.
When you connect the primary in wye configuration, then the primary line to line voltage is able to work with voltage until
7967V*root(3)=13.7kV
.What question doesn't say is the bus voltage. In that case, if you suppose that the bus voltage is 7.9kV then you are right. If you suppose that the bus voltage is 13.9kV, then the book is right. Thinking power grid, I'd say that 13.9kV is a line to line voltage to expect.