Electronic – Isolation transformer weirdness

isolationtransformer

I recently posted a question about cutting the ground wire in an isolation transformer to make it truly isolated. After reading the responses, I decided the best advice was to reconnect the ground wire and just use a three prong to two prong adapter between the isolation transformer and the DUT. After I reconnected the ground I checked and confirmed that I had ground wire continuity from the wall outlet to the transformer outlet. Then, just out of curiosity, I plugged in one of those outlet testers from Home Depot (the ones with the three lighted indicators that tell you if the outlet is wire correctly). I expected that it would say that I had an "Open Neutral" since there is no connection between primary and secondary coils, but what it said was that I had "Open Ground". I checked the tester in a house outlet and it is functioning fine.

Is there some physics about transformers that would confuse this tester or is it telling me that even though I think I have good continuity through the ground wire, it isn't good enough?

Best Answer

That's the correct indication for the transformer in its original configuration.

With a normal outlet, the neutral and the ground are bonded together at the service entrance, so the tester will light two lights: one between line and neutral and the other between line and ground, since the same voltage appears across both pairings.

With the tester plugged into the transformer, there's voltage between line and neutral created by the transformer secondary, but now there's no path between your isolated neutral and ground, so now that light on the tester no longer lights, indicating "open ground".