When meggering a three phase motor, could someone please help me understand the values we would expect to see for a motor with no insulation or ground faults.

From my understanding:

Phase-GND: should see a very high resistance (in MegaOhms)

Phase-Neutral: should see a very low resistance (near zero) since all the phases are tied together at the neutral

GND-Neutral: honestly I'm not sure…

enter image description here

Best Answer

If you follow your own logic through you'll have the answer.

Since your phase to neutral resistance is close to zero then you can consider the phase and neutral as joined together (for the purpose of this exercise).

Now if phase-GND is high resistance then netural-GND must be high too.

This is correct. There should be no connection between the windings and the machine frame.

For the benefit of the unexperienced reading this post, all these measurements are carried out with the motor disconnected from the supply.