Electronic – Sizing a transformer circuit breaker UK

transformer

I am trying to size a circuit breaker for a transformer.

The transformer is three phase 480 : 4160 V rated at 25 kVA. From my calculations there will be approximately 30 A on the primary and 3.5 A on the secondary winding.

Do the circuit breakers have to be voltage rated? Since the secondary winding is a medium voltage does that affect the type of breaker used?

I have found information on the NEC guidelines but I see that this is for the US is there any equivalent for the UK?

Will I need a circuit breaker for both the primary and the secondary winding?

Any help with this matter would be much appreciated.

Kind regards

Best Answer

Primary overcurrent protection protects the conductors and the transformer. Secondary overcurrent protection protects the conductors, not the transformer. Since this running opposite normal use, please be careful to remove any ground bonding to the 480 volt cores, and add it to the secondary 4160. You may actually be better off buying switch and fuses for the 4160 volts.