How is this ELCB connected to earth

mains

I have bought an ELCB and a mini DB board for a small solar/inverter project. My understanding is that an ELCB trips when there is a potential difference between earth and neutral. The diagrams I've seen online all show an earth connection to the ELCB, for example:

Thanks electrical-engineering-portal.com

However, when I try to connect up my ELCB, I can only see the four main connections (live and neutral, in and out). Here, pics:

Front

enter image description here

There are no other connections apart from those four. How is the ELCB earthed?

The only way I can think of is through the connection to the metal rail on which all the breakers are installed. However, the backing of the breaker does not seem to be conductive.

Best Answer

The Onesto KRC3 is a residual current circuit breaker and these types of devices operate by measuring a difference current flowing in live and neutral rather than specifically measuring a leakage current to ground.

ONESTO KRC3 230/240V 25A 300mA KRC3 Residual Current Device Leakage protector Circuit breaker

The above description is taken from here

The difference between live and neutral currents IS earth current in effect: -

enter image description here

As you can see from the above, EARTH is included but isn't needed and some devices down provide a thru-going connection for earth at all. In north America they are called ground fault circuit interrupters: -

enter image description here