APC switched rack PDU: Startup outlet state

electrical-powerpower-distribution-unit

I have an APC Switched Rack PDU powering a number of servers in a remote datacentre. After a recent power outage, I noticed that the outlets did not automatically default to the On status once power was restored. Having reviewed the Web UI, I cannot find this option.

I'm not certain of the model number (it doesn't appear to be visible in the Web UI), but I think it's this one.

Is it possible to configure these PDU units to automatically power outlets after a cold start?

Best Answer

I've only done this via SNMP set commands and I've only disabled it so the ports DON'T power on after a power failure as I've also been in the power-off/power-on/power-off situation.

snmpset -v1 -c $COMMUNITY $PDU .1.3.6.1.4.1.318.1.1.12.3.1.2.0 i -1

This tells the outlets NOT to turn on after a power failure. Change the -1 to 60 to turn all of the outlets on after 60 seconds. On the switched models you can also do a staggered start of the outlets in order to avoid a circuit overload situation. I don't have that OID handy.