Electronic – How to there be a zero sequence current in a single line to ground fault with an ungrounded neutral

faulthigh voltagepower-engineeringshort-circuittransmission line

The circuit that describes a single line to ground fault in a system with an ungrounded neutral is:
enter image description here

I neglect capacitance between phases and only look at capacitance to ground.
The definition of zero sequence current is
$$I^{(0)} = \frac{1}{3}(I_1 + I_2 + I_3)$$
But if apllied to the circuit above, Kirchoff current law should state that:$$(I_1 + I_2 + I_3) = 0$$
So how can there be a zero sequence current in this circuit? What am I missing here?

Best Answer

The parasitic phase-ground capacitance is a load in all three sequence networks. Even though your zero sequence source impedance is infinite (delta), the capacitance provides a path for sequence current to flow. In the figure below i show the 3 sequence networks for your system. The red lines show how they are interconnected for an A-phase to ground fault. This should help.

enter image description here

If you calculate the B & C phase currents in the parasitic capacitance (from the sequence currents you calculate with the above circuit) you will see the phase current path clearer.

enter image description here

UPDATE: Added further explanation on calculating the sequence components and phase currents in the fault, in the ph-ground capacitance, and from the transformer. Note the reference arrows i chose (if you use opposite direction just flip phase angle by 180):

enter image description here

enter image description here